Powerpac Iveco Range

Iveco Powered Powerpac Generating Set

Westac PowerPac Iveco powered generating sets couple the rugged and well proven reliability of the world-renowned Iveco water-cooled diesel engines to high performance alternators. They are recommended for all types of residential, commercial and industrial applications, either as prime power sources or intermittent stand-by. They provide dependable, efficient power supply options across a wide range.

60Hz 3 Phase 1800 RPM

Model Engine Prime Standby Fuel Cons
KVA KW KVA KW
   
WPI 30 8031i06 36 28.8 37 29.6 9
WPI 40 NEF45AM1 48 38.4 51 40.8 11.8
WPI 60 NEF45 SM1 68 54.4 71 56.8 16.9
WPI 70 NEF45 SM2 76 60.8 84 67.2 21.8
WPI 85 NEF45 TM1 100 80 109 87.2 26.8
WPI 100 NEF45 TM2 113 90.4 125 100 31.8
WPI 125 NEF67 SM1 140 112 148 118.4 37.8
WPI 150 NEF67 TM3 170 136 178 142.4 46.5
WPI 200 NEF 60 TE2 228 182.4 251 200.8 61.8
WPI 250 Cursor 78 TE2 271 216.8 298 238.4 78.2
WPI 300 Cursor 13 TE1 338 270.4 357 285.6 79.8
WPI 350 Curosr 13 TE2 385 308 411 328.8 89.4
WPI 400 Cursor 13 TE3 429 343.2 470 376 100.6
WPI 720 Vector 8 TE1 813 650.4 890 712  

Downloadable Data Sheet

Download PDF version of the data sheet
Download 50/60Hz Data Sheet

For your convenience we also provide a downloadable data sheet in PDF format. If you do not have suitable software for reading PDF files, Adobe Acrobat Reader is freely available from http://www.adobe.com

Notes

  1. Figures quoted are based on a power factor of 0.8.
  2. All ratings are in accordance with ISO8528-1 and ISO3046, BS5514 and DIN6271 conditions.
  3. All ratings quoted are based upon nominal 380V 3ph 50Hz and 220/440V 3ph 60Hz. Voltages outside these parameters may alter the quoted ratings.
  4. Ratings quoted are based on standard alternator. Customer preference may alter ratings to suit available frame sizes.
  5. Ratings based on Iveco supplied test data under NTP conditions. Please contact Westac Power to assess if any derate is required.
  6. Fuel consumption figures are in litres per hour at 100% prime load.
  7. All information given is for guidance only and subject to alteration without notice.