Powerpac MTU Range

MTU Powered Powerpac Generating Set

Westac PowerPac MTU powered generating sets couple the rugged and well proven reliability of the world-renowned MTU water-cooled diesel engines to high performance alternators. They are recommended for all types of residential, commercial and industrial applications, either as prime power sources or intermittent stand-by. They provide dependable, efficient power supply options across a wide range.

60Hz 3 Phase 1800 RPM

Model Engine Prime Standby Fuel Cons
KVA KW KVA KW
   
WPMTU760 12V2000G43 760 608 818 654.4 164.5
WPMTU860 12V2000G83 866 692.8 947 757.6 165
WPMTU1050 16V2000G43 1050 840 1125 900 225.8
WPMTU1100 16V2000G83 1151 920.8 1250 1000 218.4
WPMTU1180 18V2000G83 1180 944 1412 1129.6 254.4
             
WPMTU1500 12V4000G21 1550 1240 1722 1377.6 306
WPMTU1700 12V4000G81 1735 1388 1908 1526.4 350.1
WPMTU2000 16V4000G21 2114 1691.2 2323 1858.4 401
WPMTU2300 16V4000G81 2300 1840 2552 2041.6 467.5

Downloadable Data Sheet

Download PDF version of the data sheet
Download 50/60Hz Data Sheet

For your convenience we also provide a downloadable data sheet in PDF format. If you do not have suitable software for reading PDF files, Adobe Acrobat Reader is freely available from http://www.adobe.com

Notes

  1. Figures quoted are based on a power factor of 0.8.
  2. All ratings are in accordance with ISO8528-1 and ISO3046, BS5514 and DIN6271 conditions.
  3. All ratings quoted are based upon nominal 380V 3ph 50Hz and 220/440V 3ph 60Hz. Voltages outside these parameters may alter the quoted ratings.
  4. Ratings quoted are based on standard alternator. Customer preference may alter ratings to suit available frame sizes.
  5. Ratings based on MTU supplied test data under NTP conditions. Please contact Westac Power to assess if any derate is required.
  6. Fuel consumption figures are in litres per hour at 100% prime load.
  7. All information given is for guidance only and subject to alteration without notice.